PoE calculator: is the switch budget enough for your devices?
A PoE switch reserves the power of its class for each device: 15.4 W for a class 3 phone, 30 W for an access point on PoE+, up to 90 W under 802.3bt. 13, 25.5 and 71.3 W of that reach the device; the rest stays in the cable. The PoE calculator goes through your cable lengths port by port and tells you whether budget and ports are enough with headroom.
- free
- no sign-up
- runs in your browser
01 / CALCULATOR
Enter switch, cable and devices, read off the budget
Calculator · PoE budget per port and switch
Guide values based on IEEE 802.3 and manufacturer datasheets. The datasheet of your switch and measurement on the installed run are what is binding.
Runs in your browser. Nothing is sent or stored.
02 / CLASSES
PoE classes 0 to 8: what the switch delivers and what arrives
Power over Ethernet carries direct current of around 50 V over the same cable as the data. Since 2003 there has been an IEEE standard for it, which has grown in three stages: 802.3af with 13 W at the device, 802.3at with 25.5 W and 802.3bt with up to 71.3 W. Before the switch puts power on the line, it checks whether a PoE device is actually connected at the other end and asks for its class. An ordinary laptop on the same port therefore gets no voltage.
Each class has two values. The switch must deliver enough that the class power arrives at the device, even in the worst case: lowest permitted voltage and 100 m of cable with the highest permitted resistance. The difference is the loss in the cable that is allowed for. From class 5 the current flows over all four pairs instead of two, because the standard does not permit more current per pair.
| Class | from type | Pairs | at switch (af/at) | at switch (bt) | at device | Peak at device |
|---|---|---|---|---|---|---|
| 0 (no class given) | Type 1 | 2 | 15,4 W | 14 W | 13 W | 14,4 W |
| 1 | Type 1 | 2 | 4 W | 4 W | 3,84 W | 5 W |
| 2 | Type 1 | 2 | 7 W | 6,7 W | 6,49 W | 8,36 W |
| 3 | Type 1 | 2 | 15,4 W | 14 W | 13 W | 14,4 W |
| 4 | Type 2 | 2 | 30 W | 30 W | 25,5 W | 28,3 W |
| 5 | Type 3 | 4 | — | 45 W | 40 W | 42 W |
| 6 | Type 3 | 4 | — | 60 W | 51 W | 53,5 W |
| 7 | Type 4 | 4 | — | 75 W | 62 W | 65,1 W |
| 8 | Type 4 | 4 | — | 90 W | 71,3 W | 74,9 W |
Class 0 is reported by a device that gives no class; the switch treats it like class 3. 802.3bt calculates classes 1 to 3 with 50 instead of 44 V and so gets by with slightly less; the calculator cautiously reserves the older value. Peak: at most 50 ms per second. After the Ethernet Alliance overview of IEEE 802.3bt-2018, as of 14 November 2026.
Fig. 1 · Power at the switch port per class (left value) and of that at the device (right value), 802.3bt, worst case.
Type and class, switch and device
The type belongs to the device itself, the class to the individual connection. A Type 2 (PoE+) switch can deliver any class up to 4, so it can also supply a class 2 phone. Conversely, a class 6 device on a PoE+ port only gets class 4. Some devices then carry on in a reduced mode, with fewer antennas or without USB, others do not start at all. What your device does is in its datasheet; the calculator shows such a port in red.
| Type | Standard | on the market | up to class | lowest voltage | Resistance per pair set |
|---|---|---|---|---|---|
| 1 | IEEE 802.3af | PoE | 3 | 44 V | 20 Ω |
| 2 | IEEE 802.3at | PoE+ | 4 | 50 V | 12,5 Ω |
| 3 | IEEE 802.3bt | PoE++ up to 60 W | 6 | 50 V | 12,5 Ω |
| 4 | IEEE 802.3bt | PoE++ up to 90 W | 8 | 52 V | 12,5 Ω |
802.3bt also brings tricks that save budget. With Autoclass, the switch measures after power-up what the device actually draws and reserves only that much. With power demotion, a device gets a lower class when the budget runs short. And a Type 3 or 4 switch may also feed small classes over four pairs; the loss in the cable then halves. Autoclass is optional; which of these features your switch supports is in its datasheet.
03 / CABLE
How much power stays in the network cable
Every metre of copper has resistance, and the current releases heat there: loss equals current squared times resistance. An installation cable of category 5e, 6 or 6A may have at most 9.38 Ω per conductor over 100 m. With PoE, the current flows out over one pair of wires and back over a second, with two conductors in parallel in each; the loop resistance of such a pair set therefore corresponds to exactly one conductor. From class 5, two pair sets run in parallel and the resistance halves.
The calculator works out the current as the standard specifies for the switch: I = (V − √(V² − 4·R·P)) ÷ 2R, with the power P at the device, the resistance R of the run and the lowest voltage V the switch may deliver. Real switches usually output a little more voltage, so the loss is an upper limit. Copper conducts less well when warm; at 60 °C the same conductor has 16 % more resistance than at 20 °C. Patch cables are often thinner (26 AWG instead of 24) and are counted separately; the standard allows them up to 14 Ω per 100 m, and the calculator uses that.
| Length | Class 4, 24 AWG | Class 4, 23 AWG | Class 8, 24 AWG | Class 8, 22 AWG |
|---|---|---|---|---|
| 10 m | 0,26 W · 1 % | 0,2 W · 0,8 % | 0,94 W · 1,3 % | 0,59 W · 0,8 % |
| 30 m | 0,81 W · 3,1 % | 0,63 W · 2,4 % | 3 W · 4 % | 1,8 W · 2,5 % |
| 50 m | 1,4 W · 5,2 % | 1,1 W · 4,1 % | 5,3 W · 6,9 % | 3,1 W · 4,2 % |
| 70 m | 2,1 W · 7,5 % | 1,6 W · 5,9 % | 7,9 W · 10 % | 4,6 W · 6 % |
| 90 m | 2,8 W · 9,9 % | 2,1 W · 7,7 % | 11 W · 13 % | 6,1 W · 7,9 % |
| 100 m | 3,2 W · 11 % | 2,4 W · 8,6 % | 12,7 W · 15 % | 6,9 W · 8,9 % |
Percentage of port power. Class 4 at 50 V over two pairs, class 8 at 52 V over four pairs. Conductor values: 24 AWG to the standard's limit, 26 AWG with the limit for patch cables (14 Ω), 23 AWG at 7.44 Ω and 22 AWG at 5.9 Ω per 100 m, converted from the cross-section.
A series of measurements by the Pacific Northwest National Laboratory checked exactly this on nine cable models Tuenge et al. 2019. With minimum cross-sections under the US standard ANSI C137.3, losses stayed under 5 % as long as the runs averaged no more than 50 m; badly planned installations lose over 15 percent. The loss depended on the conductor cross-section; no trend was found for category or manufacturer. That is why the calculator asks for AWG and flags every run over 5 %. The table shows why: class 4 on 24 AWG is already just above that at 50 m, and class 8 over 100 m loses 12.7 W.
The follow-up study confirmed the result Tuenge et al. 2018. Bending and bundling in an open conduit cost hardly anything with 44 W luminaires below 30 °C. Heat and patch cables brought more loss. The calculator therefore asks for the warmest point on the run and adds 4 m of patch cable per run if you enter nothing else.
What matters for the cable
- Category is not cross-section. The category describes data transmission. For PoE, what counts is the AWG printed on the jacket: 24 AWG for Cat 5e and many Cat 6 cables, 23 AWG for many Cat 6A cables, 22 AWG for Cat 7 and Cat 7A.
- Copper-clad aluminium. Cheap cables marked CCA have aluminium conductors with a copper skin. Aluminium conducts considerably worse and tolerates heat and terminal clamping worse. They are unsuitable for PoE, and the calculation here does not apply to them.
- Patch cables. Flat and very thin patch cables often use 28 AWG conductors or a higher AWG number. For devices of class 5 and above, use ordinary patch cables with 26 or 24 AWG conductors instead.
- Plugs and outlets. An RJ45 plug also carries high power as long as its contacts keep within the standard's contact resistance Petroski 2016a. Up to 90 W that is enough. But anyone who pulls plugs under load damages the contacts over time Petroski 2016b. From class 5 upwards, switch the port off first.
04 / BUDGET
Budget, allocation and headroom
The datasheet states the PoE budget: the power that the switch's power supply provides for all PoE ports together. A switch with 24 ports and 185 W therefore cannot supply 24 devices of 30 W each, but at most six. What matters is how it distributes the budget.
- By class. At power-up the switch reserves the full port power of the reported class, whatever the device draws later. That is safe, but wastes budget. In the calculator's starting example that is 289 W reserved for devices that together draw at most 178 W.
- By consumption. The switch allocates what the device requests via LLDP or what it measures. That saves budget. But if consumption rises, for example when the cameras' infrared comes on at night, and the budget is full, it switches ports off. Port priority decides which ports are switched off first; door station and cameras belong at the top.
In both cases you plan with the maximum value from the datasheet. An access point's consumption varies widely with settings and load Silva et al. 2019, and a large part arises per transmitted packet Serrano et al. 2015. What an access point draws idle says little about what it needs in a full canteen. For new Wi-Fi generations the rule is: it is not the standard itself that drives demand, but more antennas, more bands and more users Dembélé 2025. The templates in the calculator are therefore graded by radio hardware.
The headroom is room for the next device and for load peaks. We leave 20 percent free; if you already know the next expansion, include it straight away. What the switch shows per port in its interface is, by the way, the power at the port, cable loss included, and the display itself has a measurement inaccuracy Perera et al. 2019. It is good for checking; for planning, use the datasheet.
05 / DEVICES
What access points, cameras and phones need
The templates in the calculator come from manufacturer datasheets. They stand for power levels, not for a purchase recommendation; you enter your own device with the class and watts from its datasheet. Where the manufacturer gives no class, the highest of the stated standard is shown, marked with an asterisk.
| Device | Example | Class | at most | reserved | From the datasheet |
|---|---|---|---|---|---|
| Access point Wi-Fi 6, 2 × 2 | UniFi U6+ | 3* | 9 W | 15,4 W | Datasheet: PoE (802.3af), at most 9 W. |
| Access point Wi-Fi 6, 4 × 4 on 5 GHz | UniFi U6 Pro | 3* | 13 W | 15,4 W | Datasheet: PoE (802.3af), at most 13 W, so right at the limit of class 3. |
| Access point Wi-Fi 6E, three bands | UniFi U6 Enterprise | 4* | 22 W | 30 W | Datasheet: PoE+ (802.3at), at most 22 W. |
| Access point Wi-Fi 7, three bands, 2 × 2 | UniFi U7 Pro | 4* | 21 W | 30 W | Datasheet: PoE+ (802.3at), at most 21 W. |
| Access point Wi-Fi 7, three bands, 4 × 4 on 5 GHz | UniFi U7 Pro Max | 4* | 25 W | 30 W | Datasheet: PoE+ (802.3at), at most 25 W; class 4 allows 25.5 W at the device. |
| Access point Wi-Fi 7 for many users | LANCOM LX-7500 | 6 | 37 W | 60 W | Datasheet: at most 37 W, 802.3bt class 6 for full operation. On an 802.3at port it runs only in a reduced mode; according to the manufacturer, two 802.3at ports together are enough for full operation. |
| Access point Wi-Fi 7, four radios, 4 × 4 | Cisco CW9178I | 6 | 47 W | 60 W | Datasheet: at most 47 W with a USB device, 38 W without; 802.3bt class 6 for full operation. On an 802.3at port, according to the datasheet, it works with 2 × 2 per band and without USB. |
| Dome camera with infrared | Axis P3265-LVE | 3 | 10,7 W | 15,4 W | Datasheet: class 3, typically 4.8 W, at most 10.7 W (at night with infrared). |
| Pan-tilt camera with infrared | Axis Q6355-LE | 6 | 51 W | 60 W | Datasheet: 802.3bt Type 3 class 6, typically 13.7 W without infrared, at most 51 W; an economy profile limits it to 30 W. |
| IP phone with colour display | Yealink T54W | 3 | 5,5 W | 15,4 W | Datasheet: 802.3af class 3, 2.2 to 5.5 W over PoE. |
| Video door station | DoorBird D2101V | 0* | 13 W | 15,4 W | Datasheet: PoE 802.3af Mode A, no class and no consumption given; calculated with the maximum of 13 W. Mode A means: power over pairs 1/2 and 3/6, which at 10/100 Mbit/s also carry the data. |
* Class not stated in the datasheet: highest class of the stated standard. Datasheets retrieved on 14 November 2026; manufacturers change values with new revisions.
Two patterns stand out. Tri-band access points with 2 × 2 sit just below the PoE+ limit, models with 4 × 4 on all bands need 802.3bt. And cameras are modest during the day: the dome camera typically draws less than half its maximum, and only at night with infrared does it get more. How many access points an area needs is worked out by the Wi-Fi planner; for halls with shelving and machinery, the guide Wi-Fi in the workshop hall helps.
06 / HEAT
Cable bundles, heat and high classes
A single cable hardly gets warm from PoE. In a bundle it is different, because each cable heats its neighbours and the heat from the middle escapes poorly. At classes 7 and 8 almost 1 A flows per pair, and from here the standards give concrete rules.
- At most 24 cables per bundle. ISO/IEC TS 29125 confirms this recommendation for remote powering and allows for a temperature rise of at most 10 K at 50 °C ambient. For Type 4 that means: make bundles smaller, if need be split them over several routes.
- At most 45 °C ambient. TIA TSB-184-A assumes this limit so that a cable rated for 60 °C keeps 15 K of room for its own heating. In lofts and unventilated cabinets that soon becomes tight.
- Not through insulation. Cables in thermal insulation hardly shed their heat. Where there is no alternative, route them singly and choose a thicker conductor.
For phones, small cameras and access points on PoE+, this rarely matters in practice. We have not found peer-reviewed measurement series on whole PoE bundles for this page; the rules above come from the standards and from the documents of the IEEE working group on 802.3bt.
07 / UPS
What the PoE switch draws from the socket
For the UPS, the PoE budget does not count. What counts is what the switch really draws: its own consumption for ports and processor, plus the PoE power including the loss in its power supply. The switch's own consumption depends on the number of occupied ports and on the load Sivaraman et al. 2014 and drops when Energy Efficient Ethernet (IEEE 802.3az) sends links without traffic into a sleep mode Christensen et al. 2010. In the datasheet it appears as power consumption without PoE.
What this means in everyday use is shown by a demonstration in schools and offices funded by the US Department of Energy Shen et al. 2022. In a classroom, the PoE system still drew 49 W with the lights off, about 15 W of that was for the switch. A laboratory comparison of two PoE lighting systems cited there arrived at 73 to 75 percent overall efficiency with 100 m of cable. Efficiencies from the datasheet often do not hit part-load operation Santos et al. 2021. The calculator therefore cautiously assumes 85 percent for the power supply and states the load of the switch. In the starting example that is about 234 W.
You enter this value in the UPS calculator as a device of its own. Do not list the PoE devices there again; they are already included in the switch's load. Incidentally, PoE does not automatically save power. In simulations, direct current in a building pays off mainly with solar panels, storage and a high distribution voltage Gerber et al. 2018; PoE at around 50 V and thin conductors is low-voltage distribution with noticeable line loss. That more power over Ethernet is changing how small devices are supplied is described in the overview by Nordman and Christensen 2016. The benefit in operation is a different one: one cable for power and data, restarting devices remotely, the consumption per port in the switch interface.
08 / METHOD
How to plan PoE for your network
- Count the devices, with datasheets. For each device note the class and highest power consumption, plus the location. Write down the next expansion at the same time.
- Measure the routes. Cable length from the cabinet to the outlet plus patch cables. Beyond 100 m you need a second distribution point closer to the device.
- Choose the standard by the highest class. Up to class 4, PoE+ is enough; for classes 5 and 6 it must be 802.3bt Type 3, for 7 and 8 Type 4. Some switches have 802.3bt on only some ports; the datasheet says which.
- Budget with headroom. Calculate by class if the switch allocates that way, and leave 20 percent free.
- Set priorities. Set the door station, cameras and reception phones to high priority, so that when supply is tight the switch turns off unimportant things first.
- Switch on the UPS. With the load from the calculator, so that phones and cameras survive a power cut.
Where the calculator stops
- Worst case. Lowest permitted voltage, maximum values from the datasheet, classes 0 to 4 over two pairs. In everyday use, consumption and loss are usually lower.
- Conductor values estimated. 24 AWG to the standard's limit, the other cross-sections converted. The tool does not include connectors and contact resistances; measurement on the installed run is more accurate.
- Switch peculiarities. Ports with different power, redundant power supplies and the exact allocation specified by the manufacturer are in the switch's datasheet.
How we build networks with switches, cabling and Wi-Fi for businesses is described under Networks. We source switches, access points and cables through hardware procurement.
09 / RESEARCH
What the research says
The thresholds in the calculator rest on measurements, not on gut feeling. Five findings support the most important decisions; the full list with review notes is further down.
- The conductor determines the loss. With a suitable cross-section and runs averaging up to 50 m, cable losses were below 5 percent. In poorly planned installations they exceeded 15 percent Tuenge et al. 2019. The calculator asks for AWG and warns when losses exceed 5 percent.
- Heat and patch cables cost too. Higher temperature raises conductor resistance, patch cables raise the loss Tuenge et al. 2018. Each is an input of its own.
- Access points draw very differently depending on load and hardware. Settings, antennas, bands and users determine the demand Silva et al. 2019 Dembélé 2025. Planning uses the maximum value.
- A PoE system has a base load. The switch draws even when all devices are idle, and in the cited laboratory comparison about a quarter was lost between socket and luminaire Shen et al. 2022. That is why the result shows the load for the UPS.
- High power needs good plugs. RJ45 carries up to 90 W if the contacts are right and are not pulled under load Petroski 2016b.
10 / FOR AI ASSISTANTS
Using this tool from an AI assistant
Assistants such as Claude or ChatGPT that speak the Model Context Protocol (MCP) can call this page’s calculation directly instead of rebuilding it. The server is public, needs no sign-in and stores nothing. The answer always includes the link to this page, the date of the data and the limits of the result.
- Endpoint
https://aureum-tech.com/mcp- Tool
werkzeug_poe_rechner- Transport
- Streamable HTTP, read-only
| Name | Required | Meaning |
|---|---|---|
switch_standard | yes | PoE standard of the switch: af = IEEE 802.3af (Type 1) (PoE, up to class 3); at = IEEE 802.3at (Type 2) (PoE+, up to class 4); bt3 = IEEE 802.3bt Type 3 (PoE++ up to 60 W, up to class 6); bt4 = IEEE 802.3bt Type 4 (PoE++ up to 90 W, up to class 8). |
budget_w | yes | PoE budget of the switch in watts according to the datasheet (total PoE power). |
poe_ports | yes | Number of PoE-capable ports on the switch. |
geraete | yes | The connected devices, one line per device type with quantity and cable length. |
zuteilung | no | How the switch allocates the budget: klasse = reserves the class power per port (safe, default); verbrauch = by LLDP or measurement. |
reserve_prozent | no | Percentage of the budget to keep free. Default 20. |
eigenverbrauch_w | no | Switch power consumption without PoE in watts, for the UPS value. Default 25. |
leiter_awg | no | Conductor cross-section of the installed cable: 24 (Cat 5e, many Cat 6 cables); 23 (many Cat 6 and Cat 6A cables); 22 (Cat 7, Cat 7A, some Cat 6A cables); 26 (thin cables and patch cables used for the whole run). Default 24. |
temperatur_c | no | Highest ambient temperature along the run in °C. Default 30. |
patchkabel_m | no | Patch cables per run together in metres (calculated with the patch cable limit of 14 Ω per 100 m). Default 4. |
Questions where an assistant should call it
- “Is a PoE+ switch with 185 W enough for four Wi-Fi 7 access points, six IP phones and four cameras?”
- “Which PoE class does a 37 W access point need, and which switch standard delivers it?”
- “How much power is lost on 90 m of Cat 5e cable with a 25 W device?”
- “How many watts must the UPS carry for a PoE switch with 300 W of connected devices?”
How the connection works and what MCP can do in your own business is explained on the page about MCP integrations.
11 / COMMON QUESTIONS
Common questions about PoE, budget and cable
How many watts do PoE, PoE+ and PoE++ deliver?
At the switch port: 15.4 W for PoE under 802.3af, 30 W for PoE+ under 802.3at, 60 W for 802.3bt Type 3 and 90 W for Type 4. At most 13, 25.5, 51 and 71.3 W of that reach the device, because the standard allows for the loss over 100 m of cable. A device must never draw more than its class allows at the device.
What is the difference between PoE class and PoE type?
The class (0 to 8) says how much power a device needs and how much the switch reserves for it. The type (1 to 4) describes the switch or the device itself: voltage, pairs, highest class. Type 1 is 802.3af up to class 3, Type 2 is 802.3at with class 4, Type 3 goes up to class 6 and Type 4 up to class 8. From class 5 upwards the current always flows over all four pairs.
Why is the PoE budget not enough although the devices use less?
Because many switches reserve by class, not by consumption. A phone drawing 5.5 W reports class 3, and the switch holds 15.4 W free for it. In the calculator's example, 15 devices draw about 178 W, but 289 W is reserved. A switch that allocates by consumption via LLDP or measurement helps, as does a bigger budget.
How long can a PoE cable be?
Like any Ethernet over copper: at most 100 m from the switch to the device, patch cables included. The standard guarantees full power over that distance. The loss grows with length: a class 4 device loses 1.4 W on 50 m of Cat 5e cable, which is 5.2 % of the port power. To go further you need a PoE extender or a switch closer to the device.
Do I need Cat 6 or Cat 6A for PoE?
For power, the conductor cross-section counts, not the category. Cat 5e with 24 AWG carries all classes up to 100 m. Thicker conductors of 23 or 22 AWG, as many Cat 6A and Cat 7 cables have, lose less and heat up less. That pays off for classes 7 and 8, on long runs and in large cable bundles. Copper-clad aluminium (CCA) does not belong in a PoE installation.
How much power does a Wi-Fi 7 access point need?
That depends on the radio hardware. According to the datasheet, tri-band models with 2 × 2 manage on 21 to 25 W and run on PoE+. Devices for many users with 4 × 4 on all bands need 37 to 47 W and so 802.3bt class 6; on PoE+ they run only in a reduced mode.
Does the PoE switch need to be on the UPS?
Yes, if phones, cameras or the door station are to survive a power cut. What counts for the UPS, though, is not the PoE budget but what the switch really draws from the socket: its own consumption plus the PoE power including power supply loss. The calculator gives this figure; the UPS calculator uses it to work out the runtime.
Where does the PoE calculator stop?
It calculates to IEEE 802.3 with the lowest permitted voltage and maximum values from datasheets, so for the worst case. How your switch distributes the budget, which ports take priority and what the installed cables really measure, we check with you on site in the Vogtland: we plan the switch and cabling and put the devices into operation.
12 / STUDIES AND SOURCES
What the tool is based on
The guide values and notes above are based on these 14 scientific papers. Each one has been checked via its DOI or the publisher’s page (most recently on 14 November 2026): it exists, it has not been retracted, and its findings still hold for this question today.
Tuenge, J.; Kelly, K.; Poplawski, M. (2019): Connected Lighting Systems Efficiency Study – PoE Cable Energy Losses, Part 1 [Revised]. Pacific Northwest National Laboratory for the U.S. Department of Energy, report PNNL-27079 (2017, revised 2019)
Finding Nine cable models on a PoE switch, measured at about 50 m and at almost zero metres: with minimum cross-sections under ANSI C137.3, the loss in the cable stayed under 5 percent as long as the runs averaged no more than 50 m. Badly planned installations can lose over 15 percent. The loss fell with a thicker conductor; no trend appeared by category, fire rating or manufacturer.
In the tool The calculator asks for the conductor cross-section in AWG instead of the category and flags every run on which more than 5 percent of the port power stays in the cable.
doi.org/10.2172/1418428 · Research report
Tuenge, J.; Kelly, K.; Chen, Y. et al. (2018): Connected Lighting Systems Efficiency Study: PoE Cable Energy Losses, Part 2. Pacific Northwest National Laboratory for the U.S. Department of Energy, report PNNL-28099
Finding Follow-up with further cables: the cross-section requirements again kept the loss under 5 percent. Bending and bundling in an open conduit hardly raised it with 44 W luminaires below 30 °C. Higher ambient temperature raises the conductor resistance and with it the loss, as do connected patch cables.
In the tool That is why the tool calculates the resistance at the chosen ambient temperature and counts the patch cables with a thinner conductor separately.
doi.org/10.2172/1512365 · Research report
Perera, I. U.; Thotagamuwa, D. R.; Freyssinier, J. P. et al. (2019): Characterization of a Power-over-Ethernet (PoE)-based LED lighting system. Light-Emitting Devices, Materials, and Applications, Proceedings of SPIE (2019)
Finding Commercially available PoE lighting systems were measured part by part: switch, cable, device and driver. Losses arise at every stage, in the cable through the voltage drop. Measured energy values and those reported by the system differed.
In the tool The page explains that the port display in the switch contains cable loss and measurement error and is not a device value; planning is therefore done with the datasheet, checking with the display.
doi.org/10.1117/12.2510019 · Conference paper
Shen, L.; Sui, D.; Lysholm, R. et al. (2022): The Demonstration of Power over Ethernet (PoE) Technologies in Commercial and Institutional Buildings. Center for Energy and Environment with NREL, final report for the U.S. Department of Energy and the Minnesota Department of Commerce
Finding PoE technology measured at six sites (offices, schools, a hotel) against conventional connections. A PoE system draws power even at rest: in one classroom it was 49 W, about 15 W of it for the switch itself. A laboratory comparison that the report cites arrived at 73 to 75 percent overall efficiency with 100 m of cable.
In the tool The UPS note therefore calculates with the switch's own consumption plus PoE power including power supply loss, not with the PoE budget from the datasheet.
doi.org/10.2172/1970746 · Research report
Santos, A.; Duggan, G.; Frank, S. et al. (2021): Endpoint Use Efficiency Comparison for AC and DC Power Distribution in Commercial Buildings. Energies 14 (18), Art. 5863
Finding Pairs of AC and DC power supplies were measured with real load profiles of office devices. Neither design was more efficient across the board; in half the cases one was ahead, in the other half the other. Efficiencies from the datasheet or at full load led to clear misestimates.
In the tool The calculator assumes the power supply efficiency cautiously and does not promise any power saving through PoE.
doi.org/10.3390/en14185863 · Journal article
Gerber, D. L.; Vossos, V.; Feng, W. et al. (2018): A simulation-based efficiency comparison of AC and DC power distribution networks in commercial buildings. Applied Energy 210, pp. 1167–1187
Finding Modelica simulation of an office building: DC distribution saved 12 percent in the base case, up to 18 percent. It brings most with a large solar installation, large storage and a high distribution voltage.
In the tool The page notes that PoE at around 50 V is low-voltage distribution with noticeable line loss; whether it saves depends on the whole setup.
doi.org/10.1016/j.apenergy.2017.05.179 · Journal article
Nordman, B.; Christensen, K. (2016): DC Local Power Distribution: Technology, Deployment, and Pathways to Success. IEEE Electrification Magazine 4 (2), pp. 29–36
Finding Overview of DC in buildings: besides 380 V systems, it is above all the rising power over Ethernet and USB that has changed the distribution of small loads. Open questions concern standards, policy and technology.
In the tool Background for the section on classification: PoE is standardised DC distribution for small devices, with rules for power and cable.
doi.org/10.1109/mele.2016.2544218 · Journal article
Silva, P.; Almeida, N. T.; Campos, R. (2019): A Comprehensive Study on Enterprise Wi-Fi Access Points Power Consumption. IEEE Access 7, pp. 96841–96867
Finding Access points from the three big manufacturers for business networks were measured across all configuration options. Consumption depends clearly on configuration; some older assumptions from the literature were not confirmed.
In the tool The templates use the maximum value from the datasheet, because actual consumption varies with settings and planning has to cover the worst case.
doi.org/10.1109/access.2019.2928754 · Journal article
Dembélé, H. (2025): Characterization of Wi-Fi Access Point Energy Consumption and the Impact of IEEE 802.11 Standard Evolutions. IEEE Access 13, pp. 126355–126375
Finding Access points from Wi-Fi 4 to Wi-Fi 7 compared: a newer standard alone does not need proportionally more power. What tips the balance are antennas and data streams, number of bands, channel width and the number of active users and networks; because each generation brings more of these, demand rises all the same.
In the tool The templates are graded by radio hardware (2 × 2, 4 × 4, three or four radios), not just by Wi-Fi generation.
doi.org/10.1109/access.2025.3590176 · Journal article
Serrano, P.; Garcia-Saavedra, A.; Bianchi, G. et al. (2015): Per-Frame Energy Consumption in 802.11 Devices and Its Implication on Modeling and Design. IEEE/ACM Transactions on Networking 23 (4), pp. 1243–1256
Finding Measurements on seven Wi-Fi devices, including routers: a large part of the energy demand arises per transmitted packet, regardless of its size. Models with a fixed base load underestimate this.
In the tool A fully loaded access point draws more than an idling one; the calculator therefore plans with full load.
doi.org/10.1109/tnet.2014.2322262 · Journal article
Petroski, J. (2016): Power over Ethernet thermal analysis with an engineering mechanics approach. 32nd Thermal Measurement, Modeling & Management Symposium (SEMI-THERM), pp. 50–56
Finding A common RJ45 plug also carries high PoE power as long as the contact resistances stay within the limits of the standard.
In the tool The page advises standards-compliant plugs and outlets, because a bad contact makes the calculation on the cable worthless.
doi.org/10.1109/semi-therm.2016.7458445 · Conference paper
Petroski, J. (2016): Thermal analysis of Ethernet connector in power applications with an engineering mechanics approach. 15th IEEE ITherm Conference, pp. 823–829
Finding The calculation shows the RJ45 plug as adequate up to 90 W. Above that, and when plugs are pulled under load and the contacts suffer, it becomes inadequate.
In the tool From class 5, the calculator reminds you to switch the port off before unplugging.
doi.org/10.1109/itherm.2016.7517631 · Conference paper
Christensen, K.; Reviriego, P.; Nordman, B. et al. (2010): IEEE 802.3az: the road to energy efficient ethernet. IEEE Communications Magazine 48 (11), pp. 50–56
Finding Describes the origin of Energy Efficient Ethernet (IEEE 802.3az): a sleep mode lowers the demand of a link when no packets are running. The authors estimate the saving in the USA alone at over 400 million dollars a year.
In the tool The page explains that the switch's own consumption counts separately from the PoE budget and falls on quiet ports with 802.3az switched on.
doi.org/10.1109/mcom.2010.5621967 · Journal article
Sivaraman, V.; Reviriego, P.; Zhao, Z. et al. (2014): An experimental power profile of Energy Efficient Ethernet switches. Computer Communications 50, pp. 110–118
Finding Three commercially available switches with 802.3az measured: their consumption depends on the number of occupied ports, on load, packet size and burstiness; a simple model reproduces this.
In the tool That is why the calculator asks for the switch's own consumption from the datasheet instead of deriving it from the PoE budget.
doi.org/10.1016/j.comcom.2014.02.019 · Journal article
Standards, authorities and manufacturer data
- Overview of 802.3bt – Power over Ethernet standard (classes, types, voltages, loop resistance) · Ethernet Alliance, December 2019
- IEEE Std 802.3bt-2018: Power over Ethernet over 4 pairs · IEEE
- Ambient temperature considerations for IEEE 802.3bt (excerpts from TIA TSB-184-A, ISO/IEC TS 29125, NEC) · IEEE 802.3bt Task Force, January 2017
- Category 5e CMR: conductor resistance below 9.38 Ω per 100 m, 24 AWG, to TIA-568.2-D · Southwire
- PoE Connected Lighting System Energy Losses in Ethernet Cables, Part 2 (summary) · U.S. Department of Energy
- UniFi U6+, U6 Pro, U6 Enterprise, U7 Pro, U7 Pro Max: Tech Specs · Ubiquiti
- LX-7500 datasheet and LCOS LX manual on Dual-PoE · LANCOM Systems
- CW9178I Datasheet: power consumption and operation on 802.3at · Cisco Meraki
- Datasheets P3265-LVE and Q6355-LE · Axis Communications
- Datasheet SIP-T54W · Yealink (copy at the provider Intermedia)
- Datasheet D2101V · DoorBird
13 / MORE TOOLS
Still have a question?
- AT-W2 · Home & business
Windows 10 check
Does this PC still get security updates, and what needs doing by October 2027? - AT-W3 · Home & business
Wi-Fi planner
How many access points or mesh units does your home, office or warehouse need? - AT-W4 · Businesses
IT emergency check
How quickly could your business get back to work after an outage? - AT-W5 · Businesses
E-mail check
Are your e-mails landing in spam? Your domain’s SPF, DKIM and DMARC in plain language. - AT-W6 · Businesses
UPS calculator
Which UPS keeps your server, router and till running long enough during a power cut? - AT-W8 · Businesses
XRechnung viewer
Received an XRechnung as an XML file? This makes it readable without the file leaving your computer.
Have your result? Send us a copy. We check the switch and cable routes and put the network into operation, in Rodewisch and throughout the Vogtland.
+49 3744 4399760[email protected]Mon–Fri 8:00–17:00 · Straße der Jugend 5, 08228 Rodewisch