Tool AT-W6REV. 2026-A

UPS calculator: which UPS keeps a server, NAS and till running?

A UPS has to do two things: carry the real power of all connected devices with 25 per cent reserve, and last long enough for the server and NAS to shut down cleanly. Ten minutes is usually enough for that. For a router, switch and NAS, a line-interactive UPS with 700 VA is often sufficient. The UPS calculator adds up your devices and gives you the power class, the type and an honest runtime range.

  • free
  • no sign-up
  • runs in your browser

Enter your devices, read off class and runtime

Calculator · device list and runtime

The calculator works with guide values and typical battery sets. It tells you which class and type fits; the exact runtime is in the runtime chart of the unit you buy.

Step 1Which devices should stay on battery in a power cut?

A small office is pre-filled. The watts are guide values in operation; a measured value of your own is always better.

    How do I find out the real consumption?
    • Not the rating plate. It states the most the power supply can deliver. A server with a 500 W power supply often draws only a quarter of that in everyday use.
    • Plug-in power meter. An adapter plug with a display, between the wall and the device for a few days. Take the highest value in normal operation.
    • Data sheet. What you want is the power consumption in operation or “under load”, not the size of the power supply.
    • Server remote management. The management interface of many servers shows the current power consumption.
    Step 2How long should the UPS last?

    Anyone who bridges an outage still has to shut down afterwards. The calculator therefore adds 10 minutes to every bridging time.

    Step 3Mains and installation

    Load on battery

    —

    Enter at least one device with a wattage.

    Guide values, as of 13 November 2026. The runtime chart of the unit is what counts. We obtain suitable units and replacement batteries through our hardware ordering; the easiest way to send us your device list is to copy it into the contact form.

    Runs in your browser. Nothing is sent or stored.

    Watts or VA: which number on the UPS counts?

    Every UPS carries two power ratings. VA is the apparent power, W the real power, that is, what your devices actually consume. The ratio of the two is called the power factor. On small UPSs that show only their VA figure in large print on the front, it is often 0.6: 1000 VA becomes 600 W. Schneider Electric itself recommends this rule of thumb, in White Paper 15 (“Watts and Volt-Amps”). Newer units and online UPSs reach 0.9 to 1, so the same 1000 VA then carry 900 W or more. The gap comes from power supplies without power factor correction, which draw their current in peaks rather than as a sine wave Mansoor et al. 1995.

    For you this means: compare watts with watts. The total of your devices plus reserve must be below the W rating on the data sheet. The VA figure on the box only helps with rough sorting. The graphic shows a case that comes up all the time in practice: two units with identical labels, only one of which is enough.

    The 25 per cent reserve has two reasons. Manufacturers recommend loading a UPS in continuous operation to no more than 80 per cent, and that is exactly what produces this margin. Networks also grow. The second switch or the bigger NAS usually arrives before the UPS has reached the end of its life.

    NEED 700 WBOX1000 VAFACTOR 0.6not enough600 WFACTOR 0.9enough900 W05001000 W / VAEXAMPLE: 560 W LOAD + 25 % RESERVE = 700 W

    Offline, line-interactive or online: the three types

    The standard EN IEC 62040-3 classifies UPSs by how strongly their output depends on the mains. The abbreviations VFD, VI and VFI appear on many data sheets, often in small print. Anyone who knows them can compare units from different manufacturers on the same basis.

    The three types under EN IEC 62040-3
    TypePrincipleTransferSuitable forLimit
    Offline (standby)
    VFD
    Passes the mains power through and switches to battery only when it fails.up to about 10 msRouter, modem, single PCDoes not correct under- or overvoltage; often only a stepped sine wave.
    Line-interactive
    VI
    Passes the power through, but continuously smooths out voltage fluctuations with a regulating transformer.a few millisecondsNAS, small server, phone system, tillFollows the mains frequency; on a standby generator it often switches to battery.
    Online (double conversion)
    VFI
    Continuously generates the output voltage from direct current, independently of the mains.no transfer gapSeveral servers, virtualisation, standby generator, unstable mainsMore expensive, higher power consumption, audible fan.

    For most small businesses, line-interactive is the right choice. It smooths out under- and overvoltage without straining the battery at every blip, and it is economical in operation. Online units protect most thoroughly, but pay for it in efficiency Aamir et al. 2016. They are worthwhile with several servers, with a virtualisation host and wherever a standby generator feeds the system. The reason is inconvenient but important: a generator does not hold the frequency as steadily as the mains, and a line-interactive UPS then keeps switching to battery until it is empty.

    A second point that is often overlooked when buying is the waveform at the output. Cheaper units produce a stepped approximation of a sine wave on battery. Server and PC power supplies with active power factor correction (PFC) can shut down on it at the moment of switching, which is exactly when the UPS was bought to help. If the data sheet says “pure sine wave”, that is ruled out. The calculator asks for a sine wave as soon as a server, PC or till is in the list.

    How long does a UPS really last?

    The runtime depends less on the UPS than on its batteries, and they behave differently from what you might expect. A lead-acid battery gives up less energy the faster it is discharged. A typical 12 V / 9 Ah UPS block has 108 Wh on paper. If it is drained in ten minutes, only about 46 Wh come out according to the manufacturer’s data sheet; over an hour it is 69 Wh. That is the Peukert effect. It explains why half the load brings more than twice the runtime, and why runtimes can never simply be worked out by proportion. Even the Peukert formula itself holds only at constant load and temperature Doerffel and Sharkh 2006; the calculator therefore reads the measured curve from the data sheet.

    A 12 V / 9 Ah battery block at 25 °C (data sheet CSB HR1234W, discharge down to 1.67 V per cell)
    Empty afterPowerEnergyShare of rated value
    5 minutes438 W37 Wh34 %
    10 minutes277 W46 Wh43 %
    15 minutes206 W52 Wh48 %
    30 minutes119 W60 Wh55 %
    60 minutes69 W69 Wh64 %
    90 minutes50 W75 Wh69 %

    Then there are temperature and age. Lead-acid batteries are designed for 20 to 25 °C. Schneider Electric gives as a rule of thumb that 8 °C more halves the service life: a battery that lasts four years at 25 °C is finished after two years in a plant room at 33 °C. Behind this lies mainly grid corrosion, which increases with temperature Misra and Williamson 1995. The service life cannot be predicted exactly from this, however Bullough et al. 1987. The battery manufacturer CSB rates the common block at 3 to 5 years under Eurobat. Replace the battery at the latest when its capacity falls below 80 per cent of the rated value; corrosion and water loss also eat away at a battery that was never used Ruetschi 2004. The calculator therefore plans with these 80 per cent, so that the runtime is still enough in the fourth year, and with 85 per cent inverter efficiency.

    A worked example: a tower server, a four-disk NAS, a router and a switch draw about 182 W together. A 700 VA UPS keeps that going for 10 to 34 minutes, depending on the battery set and age. That is certainly enough to shut down. One hour of bridging, by contrast, needs about 480 Wh of nominal battery energy, which is 5 blocks and so a unit with extra batteries. Anyone who really wants to keep working for hours should plan a standby generator.

    What belongs on the UPS, and how much does it draw?

    What belongs on the battery outlets is whatever holds data or keeps you reachable: servers, NAS, till and the network chain of modem, router and switch. The router needs hardly any watts, yet it decides whether phone and card payments survive the bridging time. Workstations and monitors are a matter of judgement; they are not needed for the clean shutdown of the central devices, they only cost runtime.

    Guide values in operation, as of 13 November 2026
    DeviceWattsConnection to the UPSNote
    Tower server (1 processor)120 WIEC mains lead (C13)
    1U rack server200 WIEC mains lead (C13)Two power supplies? Connect both to the UPS; the load is shared.
    2U rack server350 WIEC mains lead (C13)Two power supplies? Connect both to the UPS; the load is shared.
    NAS with 2 disks15 WSchuko, often a plug-in power supply
    NAS with 4 disks35 WSchuko, often a plug-in power supply
    Router (e.g. Fritzbox)12 WSchuko, often a plug-in power supply
    Fibre ONT or modem6 WSchuko, often a plug-in power supply
    Switch without PoE15 WSchuko, often a plug-in power supply
    Switch with PoE (without end devices)30 WIEC mains lead (C13)Base load only. Enter PoE devices individually; the PoE budget on the data sheet is a maximum, not consumption.
    Wi-Fi access point (PoE)12 Wvia the PoE switch
    Firewall (desktop unit)20 WSchuko, often a plug-in power supply
    Phone system25 WSchuko, often a plug-in power supply
    IP phone (PoE)4 Wvia the PoE switch
    IP camera (PoE)7 Wvia the PoE switchWith infrared night light, closer to 10 W.
    Camera recorder (NVR)25 WSchuko, often a plug-in power supply
    Office PC60 WIEC mains lead (C13)
    Monitor, 24 inch18 WIEC mains lead (C13)
    Till system (PC, receipt printer, card terminal)60 WSchuko, often a plug-in power supply
    Laser printer–not on the UPSThe fuser unit draws many times its normal power when heating up.

    The values are guide values for everyday use, not rating plate figures. The rating plate states the most the power supply can deliver; one server that was measured stayed below 60 per cent of that even under maximum load Fan et al. 2007. Anyone who adds up the rating plates ends up with a UPS that is three sizes too big, and with runtime figures that have nothing to do with reality. A plug-in power meter for a few days, or the figure “in operation” from the data sheet, is better.

    Access points, IP phones and cameras get their power over the network cable by PoE. Their load therefore flows through the switch to the UPS, and with a surcharge: under IEEE 802.3af the switch port must supply 15.4 W so that 12.95 W arrive at the device. The calculator therefore counts PoE loads separately and with a 20 per cent surcharge. The PoE budget on the switch’s data sheet is a maximum and not consumption. What a PoE switch and its devices really draw from the socket is worked out by the PoE calculator; enter that value here as one device, instead of the switch and the PoE devices.

    Automating the shutdown: USB, network card, NUT

    A UPS without a data connection only postpones the hard crash. When the battery is empty, the NAS goes off just as it would without a UPS, only later, and usually at night when nobody is there. Only the signal from the UPS turns battery time into a clean shutdown.

    For a single device, the USB cable supplied with the UPS is enough. NAS systems and server operating systems detect the UPS through it and shut themselves down. If several devices have to shut down, there are two ways. Either the UPS gets a network card that notifies all devices directly. Or the NAS is connected to the UPS by USB and passes the power cut on as a network UPS server. Behind this there is usually NUT (Network UPS Tools), an open standard that Linux servers and many virtualisation hosts also understand.

    With a virtualisation host the order also matters: first the virtual machines, then the host, last the NAS on which they may be stored. That takes longer than with a single device, and that is exactly why the tool builds in 10 minutes.

    BY USBMAINS FAILSUPS ON BATTERYNAS SHUTSDOWNCLEAN OFFPASSED ON OVER THE NETWORKNAS AS UPSSERVERSIGNAL ONNETWORKSERVERS AND VMSCLEAN OFFBY USBMAINS FAILSUPS ON BATTERYNAS SHUTS DOWNCLEAN OFFPASSED ON OVER THE NETWORKNAS AS UPS SERVERSIGNAL ON THE NETWORKSERVERS AND VMSCLEAN OFF
    FIG. 2 · SHUTDOWN CHAIN IN A POWER CUTGOLD = WHERE THE SIGNAL STARTS

    How to set it up

    1. Connect. Attach the USB cable or network card and switch on UPS support in the NAS or server.
    2. Set the timing. Shut down after two to three minutes on battery, rather than waiting until “battery low”. Short blips are then ridden out, and the battery still has reserve.
    3. Register further devices. Enter servers and hosts as recipients on the network UPS server or in the UPS manufacturer’s software.
    4. Test. After close of business, pull the UPS’s mains plug and watch whether the chain runs through. A shutdown that has never been tested is only an intention.
    5. Configure the restart. In the server BIOS, set whether it starts by itself when power returns. Order: router, switch, NAS, server, workstations.
    6. Plan the battery replacement. Write the installation date on the UPS and put the replacement after three to five years in the calendar.

    Why UPSs fail in small businesses

    • “The UPS has been beeping for months.” Usually the battery is at the end of its life. A UPS with a dead battery switches off at the first blip, which makes it worse than none at all.
    • The USB cable is still in the box. Then the UPS lasts only as long as the battery does, and the NAS still shuts down abruptly.
    • Surge-protected power strip behind the UPS. Several manufacturers prohibit this in their manuals. At the output, devices belong directly in the sockets.
    • Wrong sockets used. Many small UPSs also have sockets with surge protection only, without battery. The NAS then reliably ends up in the wrong one.
    • The UPS sits in the warm corner. Directly behind a server’s exhaust air, the battery ages twice as fast.
    • Bought by VA only. At power factor 0.6, a 1000 VA UPS carries just 600 W. Anyone who compares watts with VA buys too small.

    What the research says

    The guide values in the calculator are not gut feelings. Six findings from journals and conferences support the most important decisions; the full list with its review notes is further down.

    • The short outage costs more than the long one. For the USA, one estimate puts the cost of outages at around 80 billion dollars a year, mostly for businesses, and short interruptions account for the larger part LaCommare and Eto 2006. That is why the calculator is set to “shut down cleanly only”: for the common case, minutes are enough.
    • Computers react to blips. In laboratory tests with voltage sags and short interruptions, the behaviour of PCs depended strongly on the device and the state of the mains Djokic et al. 2005. A UPS removes this uncertainty.
    • The rating plate is misleading. Measured peaks lie far below it Fan et al. 2007, and even with almost no work, servers still draw about half of their full power Barroso and Hölzle 2007. The calculator therefore uses a fixed operating value: at night in a power cut, a server draws hardly less than during the day.
    • Batteries age even at rest. Corrosion and water loss eat away at capacity Ruetschi 2004, and heat accelerates the corrosion Misra and Williamson 1995. The calculator plans with 80 per cent remaining capacity.
    • Runtime is not a number you can calculate from a formula. The Peukert equation holds only at constant load and temperature Doerffel and Sharkh 2006, and predictions based on temperature remain imprecise Bullough et al. 1987. The result is therefore a range.
    • The type determines protection and consumption. Review papers on UPS topologies classify offline, line-interactive and online the way the table above does Bekiarov and Emadi 2002 Aamir et al. 2016.

    What the calculator does not know

    • The battery set of your unit. The runtime range is based on typical battery sets per class. The runtime chart on the data sheet is what counts.
    • Your real consumption. The presets are guide values. A measured value beats every one of them.
    • The electrics. Fusing, circuits and lightning protection are a matter for the electrician, as is any permanently wired UPS above 3000 VA.

    Further reading

    Why the two-second blip is more dangerous than the long outage is explained in the guide Power cuts at work. How well your business copes with an outage overall is checked by the IT emergency check, and whether the backup is still sound afterwards is settled by the 3-2-1 rule. We plan servers and NAS under Servers & virtualisation, switches and PoE under Networks. We obtain UPS units and replacement batteries through the hardware ordering, and what setup and testing cost is on the price list.

    Using this tool from an AI assistant

    Assistants such as Claude or ChatGPT that speak the Model Context Protocol (MCP) can call this page’s calculation directly instead of rebuilding it. The server is public, needs no sign-in and stores nothing. The answer always includes the link to this page, the date of the data and the limits of the result.

    Endpoint
    https://aureum-tech.com/mcp
    Tool
    werkzeug_usv_rechner
    Transport
    Streamable HTTP, read-only
    Inputs
    NameRequiredMeaning
    geraeteyesAll devices that should be on the UPS in a power cut. Enter PoE devices (ap, ipphone, kamera) individually.
    zielnoBridging time: “aus” = shut down cleanly only (default); “10”, “15”, “30” or “60” minutes of continued running, then shut down.
    netz_unruhignotrue if the power often flickers or a standby generator feeds the system. An online UPS is then recommended.
    serverschranknotrue if a 19-inch cabinet is available (rack form factor).

    Questions where an assistant should call it

    • “Which UPS do I need for a small server, a NAS and the Fritzbox?”
    • “Is a 1000 VA UPS enough for two 1U rack servers?”
    • “How long will a UPS keep my NAS and the switch running in a power cut?”
    • “Do I need an online UPS if we have a standby generator?”

    How the connection works and what MCP can do in your own business is explained on the page about MCP integrations.

    Common questions about UPSs

    How big does a UPS for a server and NAS need to be?

    Add up the power of all devices in operation, add 25 per cent reserve and compare the result with the UPS’s watt rating. Example: a tower server, a four-disk NAS, a router and a switch draw about 182 W together, 228 W with reserve. The smallest common class, 700 VA, already carries that, even at a power factor of 0.6. A larger class mainly gives you more runtime.

    What is the difference between VA and watts on a UPS?

    VA is the apparent power, watts the real power your devices actually consume. The ratio is called the power factor. Small UPSs often have 0.6, so 1000 VA becomes 600 W; newer units and online UPSs reach 0.9 to 1. What counts is the watt rating on the data sheet: the total of your devices plus 25 per cent reserve must stay below it.

    How long does a UPS last in a power cut?

    Small UPSs typically last 5 to 30 minutes, depending on the load. At full load only a few minutes are often left; at half load it is more than twice as long, because lead-acid batteries give up more energy when discharged slowly. A 12 V / 9 Ah battery block delivers about 46 Wh in ten minutes, about 69 Wh over an hour. Plan for the time to shut down, not the time to keep working.

    When does the battery of a UPS need replacing?

    Common UPS batteries are rated by Eurobat for 3 to 5 years at 20 °C. Heat shortens that considerably: 8 °C more halves the service life. Replace the battery at the latest when its capacity falls below 80 per cent of the rated value; many UPSs report this through their self-test. Write the installation date on the unit, and the replacement can be planned instead of being a chance discovery.

    Can a laser printer be connected to the UPS?

    No. While warming up, the fuser unit of a laser printer briefly draws many times its normal power. A small UPS is overloaded by this or discharges needlessly; Schneider Electric expressly advises against it. The printer gets its own wall socket. The same applies to fan heaters, kettles and coffee machines, which is why the calculator does not count such devices at all.

    Do I need an online UPS?

    For a router, NAS and a small server, a line-interactive UPS with a sine-wave output is usually enough. An online UPS (VFI under EN IEC 62040-3) is worthwhile if a standby generator feeds the system, the mains often flickers or several servers with virtualisation are connected. It works without a transfer gap, but costs more, uses more power itself and has an audible fan.

    How does a NAS shut down automatically in a power cut?

    The UPS is connected to the NAS by USB, and UPS support is switched on in the NAS’s power settings. There you set after how many minutes on battery it shuts down; two to three minutes is a good value. Synology and QNAP can pass the signal on to other devices as a network UPS server. Then test it once: pull the UPS’s plug and watch.

    Does the UPS calculator replace planning on site?

    For choosing the class and type it is usually enough. It works with guide values and typical battery sets; the exact runtime is in the runtime chart of the unit you buy. On site we measure the real load, check the circuit and the location, and set up the shutdown with a test. Above 3000 VA, or for hours instead of minutes, we plan together with the electrician.

    What the tool is based on

    The guide values and notes above are based on these 11 scientific papers. Each has been checked through its DOI or the publisher's page (last checked on 13 November 2026): it exists, it has not been retracted, and its finding still holds for the question today.

    1. Fan, X.; Weber, W.-D.; Barroso, L. A. (2007): Power provisioning for a warehouse-sized computer. Proceedings of the 34th Annual International Symposium on Computer Architecture (ISCA), pp. 13–23

      Finding A server’s rating plate figure reflects the size of the power supply, not consumption. In the measured example, a server under maximum load reached less than 60 % of its rating plate value, and at idle less than half of its actual peak.

      In the tool The presets are guide values in operation, and the calculator asks for confirmation if a single device over 1000 W is entered.

    2. Barroso, L. A.; Hölzle, U. (2007): The Case for Energy-Proportional Computing. Computer (IEEE), 40 (12), pp. 33–37

      Finding Servers rarely idle and rarely run at full load, mostly somewhere between 10 and 50 % utilisation. Even an economical server still needs about half of its full power with almost no work.

      In the tool That is why the tool uses a fixed operating value per server instead of an idle value: at night in a power cut, it draws hardly less than during the day.

    3. Mansoor, A.; Grady, W. M.; Staats, P. T. et al. (1995): Predicting the net harmonic currents produced by large numbers of distributed single-phase computer loads. IEEE Transactions on Power Delivery, 10 (4), pp. 2001–2006

      Finding Computer power supplies without power factor correction draw not a sinusoidal current but current peaks with strong harmonics. The paper quantifies how these currents from many office computers add up in a building.

      In the tool Background to the distinction between watts and VA: such loads strain a UPS more than their wattage suggests.

    4. Djokic, S. Z.; Desmet, J.; Vanalme, G. et al. (2005): Sensitivity of personal computers to voltage sags and short interruptions. IEEE Transactions on Power Delivery, 20 (1), pp. 375–383

      Finding In extensive laboratory tests, PCs were exposed to voltage sags and short interruptions, under ideal and real mains conditions and when large motors started. According to the authors, whether a PC fails depends strongly on what counts as malfunction.

      In the tool Explains why the calculator recommends a UPS even for “shut down only”: the short blip is the real risk for running devices.

    5. LaCommare, K. H.; Eto, J. H. (2006): Cost of power interruptions to electricity consumers in the United States (US). Energy, 31 (12), pp. 1845–1855

      Finding For the USA, the estimate comes to around 80 billion dollars a year in outage costs, most of it for businesses. Short, frequent interruptions contribute more to the costs than the rare long outages.

      In the tool Supports the default “shut down cleanly only”: against the frequent short outage, minutes are enough, not hours.

    6. Ruetschi, P. (2004): Aging mechanisms and service life of lead–acid batteries. Journal of Power Sources, 127 (1–2), pp. 33–44

      Finding Lead-acid batteries age through several mechanisms side by side, among them corrosion of grids and connectors and loss of water. Overcharging accelerates both.

      In the tool The reason for the ageing factor: the calculator plans the runtime with 80 % remaining capacity, not with the as-new state.

    7. Misra, S. S.; Williamson, A. J. (1995): Impact of grid corrosion in valve regulated lead-acid battery on standby float service. Proceedings of INTELEC 95, 17th International Telecommunications Energy Conference, pp. 360–363

      Finding Grid corrosion and drying out are among the main causes of failure in sealed lead-acid batteries in standby operation. Grid growth follows an Arrhenius relationship with temperature in the range studied, so heat shortens the service life in a predictable way.

      In the tool Supports the temperature note on the page: a UPS does not belong in the warm corner behind a server’s exhaust air.

    8. Bullough, R. P.; Edwards, W. H.; Harrison, A. I. (1987): Stationary Valve Regulated Sealed Lead-Acid Batteries: can the Arrhenius Equation be used to Predict Product Life. INTELEC '87, Ninth International Telecommunications Energy Conference, pp. 123–127

      Finding High-temperature tests on sealed lead-acid batteries gave contradictory service-life predictions via the Arrhenius equation. Presumably several ageing processes determine the service life at the same time.

      In the tool That is why the page states “8 °C more halves the service life” expressly as a rule of thumb and plans the battery replacement by calendar and self-test.

    9. Doerffel, D.; Sharkh, S. A. (2006): A critical review of using the Peukert equation for determining the remaining capacity of lead-acid and lithium-ion batteries. Journal of Power Sources, 155 (2), pp. 395–400

      Finding The usable capacity of a battery depends on the discharge rate. The Peukert equation reproduces this reliably only at constant current and constant temperature.

      In the tool The calculator therefore uses no Peukert formula but the measured discharge curve from the battery data sheet, and gives a range instead of a number of minutes.

    10. Bekiarov, S. B.; Emadi, A. (2002): Uninterruptible power supplies: classification, operation, dynamics, and control. APEC 2002, Seventeenth Annual IEEE Applied Power Electronics Conference and Exposition, pp. 597–604

      Finding The paper classifies static UPSs by their topology and describes the operation and control of the types and their typical weaknesses.

      In the tool It is the basis of the types table, alongside the standard EN IEC 62040-3.

    11. Aamir, M.; Kalwar, K. A.; Mekhilef, S. (2016): Review: Uninterruptible Power Supply (UPS) system. Renewable and Sustainable Energy Reviews, 58, pp. 1395–1410

      Finding The review compares UPS topologies by power, size, cost and efficiency. Online units protect best but have lower efficiency; line-interactive units are inexpensive and compact.

      In the tool Supports the recommendation to equip small businesses with line-interactive units and to reserve the online UPS for generators, unstable mains and several servers.

    Standards, authorities and manufacturer data

    Mon–Fri 8:00–17:00

    Do you have your device list? Send it to us. We will tell you which unit fits, obtain it and set up the automatic shutdown with a test, in Rodewisch and throughout the Vogtland.

    +49 3744 4399760[email protected]

    Mon–Fri 8:00–17:00 · Straße der Jugend 5, 08228 Rodewisch

    Get help choosing a UPS
    +49 3744 4399760Mon–Fri 8:00–17:00
    CallCallback

    PARTS LIST · SHEET 1/1

    What this page is made of

    Values measured at build time. With JavaScript, your browser measures them again live.

    ITEMPARTTYPESIZE
    01index.htmlDocument≈ 29 kB
    02styles.cssStylesheet≈ 20 kB
    03scripts.jsScript≈ 13 kB
    04archivo-variable.woff2Font≈ 58 kB
    05ibm-plex-mono.woff2Font≈ 30 kB
    06favicon.svgImage< 1 kB

    Advertising or analytics cookies: none. Without your consent, the page loads nothing from third-party servers apart from Cloudflare, our delivery service. Fonts, scripts and images are hosted by us. That is how we build your IT, too.

    OUTSIDE OFFICE HOURS

    Feel free to call anyway

    Our regular office hours are Monday to Friday, 8:00–17:00.

    In the evening and at weekends the number is forwarded to us, and often someone will pick up. We cannot promise that, though.

    If nobody answers, leave a short message on the voicemail: your name, your number and what it is about. We will call back as soon as we can, on the next working day at the latest.

    The call costs nothing. If someone has to start work straight away outside office hours, the surcharge in the price list applies.

    Call now+49 3744 4399760

    Prefer to write? Use the contact form or e-mail [email protected]. We will read it on the next working day.

    DIAGNOSIS · AT-K2

    What do you need help with?

    ↵ SELECTESC CLOSECALL: +49 3744 4399760

    Custom settings

    Which services may load?

    Strictly necessary

    The choice you make here and your settings for colour scheme and motion. These are kept as small entries on your device and are never sent to a server. They are needed for the site to work and therefore cannot be switched off.